SK08-WAQ
ETS-Application
DOWNLOAD ETS Application
Technical data
Technical Data - SK08-WAQ
Measured Data | pH value ( concentration of hydrogen ion ) ORP ( redox potential) Operating time in hours |
Sending Options | no sending, cyclical sending when change occurs |
Parameter | Cyclical sending with variable periods, sending when change occurs with hysteresis |
Object type ph | 1-Byte unsigned, 2-Byte float, 4-Byte float |
Object type ORP | 2-Byte signed, 2-Byte float, 4-Byte float |
Object type Laufzeit | 2-Byte unsigned |
Object type Wassertemperatur | 1-Byte signed, 2 Byte signed, 2 Byte-float, 4 Byte-float |
Object type Kontakteingänge | 1-Bit bool |
|
|
Controller Modi | Steady PI controller Switched PI controller (PWM) Two-Position controller Two-Position controller Pulsed |
Parameter Steady PI controller | Setpoint, reset time, proportional factor, controller mode |
Parameter Switched PI controller (PWM) | Setpoint, reset time, proportional factor, controller, cycle duration, threshold pitch |
Parameter Two-Position controller | Setpoint, differential gap, controller mode |
Parameter Two-Position controller Pulsed | Setpoint, differential gap, controller mode , cycle duration, duty cycle |
Lock Function | All controller parameterizable as enable or lock |
Controller Variables Output | depends on Controller Modi 1-Byte unsigned, 1-Bit Switch |
Setpoint value send cyclical | None or 10-250 seconds, parameterizable |
|
|
Limits: pH, ORP, operating time, water temperature | Lower limit, Upper limit |
|
|
Auxiliary value | Setpoint, Upper limit or Lower limit |
Bus power failure | Saving changed auxiliary quantities, parameterizable |
|
|
Calibration | pH 7 - Zero pH X - Transconductance ORP X - Transconductance Operating Time - Reset |
|
|
Ambient Temperature Electronic Measuring Equipment Casing | Operation: -20 .. +55 °C Storage: -20 .. +85°C |
Ambient Humidity | 0 .. 95% rH not condensating |
Accuracy pH | ± 0,1 |
Resolution pH | ± 0,01 |
Accuracy OPR | ± 10mV |
Resolution OPR | ± 1mV |
Accuracy water temperature | ± 1°C |
Resolution water temperature | ± 0,01°C |
|
|
Operating Voltage | KNX bus voltage 21 .. 32VDC |
Power Consumption | approx. 240mW ( at 24VDC ) |
Auxiliary Supply | not required |
Bus Coupler | integrated |
Start-up with ETS | ARC_S8 Product: S8-WAQ |
Curcuit Points | KNX 2-pole clamps ( red / black ) |
Protection Class | IP54/65 |
Assembly Type Transducer | Assembly with 2 screws finery |
Casing Transducer | ABS plastic grey |
Casing Dimensions | ( 115 x 65 x 55 ) mm ( L x W x H ) |
Article number without sonde | 30801000 |
Article number with sonde | 30801001 |
|
|
Electrode Set | Single-rod measuring cell, gel-filled, low-maintenance for standard applications pH: HI2114P-2 ORP: HI3214P-2 |
Electrode thread | 3/4“ x 16UNF |
Electrode cable | 2m with BNC plug |
Article number | 91110020 |
|
|
Temperature probe | PT1000 not included, please order separately, Price catalogue chapter Z |